1234 Your Street

Canton, MI, 48188

November 26th, 2019

INSPECTED BY

Matthew Cottenham

PREPARED FOR

Your Name

A) In Attendance

Client

Approximate Humidity

76%

Approximate Temperature

44° F

C) Type of Building

Commercial

D) Weather Conditions

Dry

Estimated Square Feet

32000

Weather Conditions

Light rain overnight.

Year Built

1997

General Information

Dear Your Name ,

The following is your inspection report for the property located at Property Address that was conducted for you on Inspection Date at Inspection Time.

The report is designed to be clear and easy to understand. Please take the time to review it carefully. If there is anything you would like us to explain please further, feel free to call us at (734) 331-3269 or email us at [email protected] and we would be happy to answer any questions you may have.

Throughout this report you will see the following types of comments:

  • General Information - These are comments that give general information about a component or system.
  • Limitations - These are comments that describe a limitation to the inspection. These are items that you may wish to have re-inspected (for a fee) once the limitation is removed and before waiving your inspection contingency.
  • General Maintenance - These are items that will need continued maintenance to keep them in good working order. These items may or may not require a professional contractor. It is important to note if you are not qualified or do not feel comfortable you should always hire a professional.
  • Recommended Upgrade - These are items that no longer meet today's building standards and do not affect the health and safety of the home or its occupants.
  • Further Evaluation - These are items that show signs that a defect may exist. However, the inspector was unable to determine if a repair is needed. These items should be evaluated by a qualified licensed contractor prior to waiving your inspection contingency.
  • Repair or Replace - These items are not functioning as they should and need to be repaired or replaced by a qualified licensed contractor.
  • Safety - These are items that pose a safety hazard that could lead to injury or death. These items need to be repaired or replaced by a qualified licensed contractor immediately.

No matter the type of comment is, we recommend every item should be taken into consideration and a plan of action decided before waiving your inspection contingency.

We thank you for the opportunity to be of service to you.

Sincerely,

Trademark Home Inspection, LLC

Scope of Work

Standards of Practice

We have inspected the property per the International Association of Certified Home Inspectors (InterNACHI's) Standards of Practice (SOP) which can be viewed at the following link https://www.nachi.org/comsop.htm#5 and throughout this report.

Limitations

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

Plans, Permits, and Municipality Documents

If the client would like documents reviewd, It is the client's responsibility to obtain copies of all documents and provide them for the inspector. These documents are most often obtained from the seller or from local government offices. The inspector is not responsible for gathering or paying for copies of appropriate documents to be reviewed unless these tasks are specifically assigned to the inspector in the Scope of Work Agreement.

Life Expectancy

The inspector does not make estimates to the life span or how long a component of the home has left before it needs to be repaired or replaced. Many factors need to be considered when making such estimates, such as the age, how well the component has been maintained, how frequently the components have been used etc... Most of which the inspector could never know. As a reference we have posted a Life Expectancy Chart on our website which you can view at the following link https://trademarkhomeinspection.com/lec/

Not For Third Party Use

This report is not intended for use by anyone other than the client named on this report. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's authorized and/or unauthorized distribution of the inspection report.

1 · Roofing Section

Roofing Section

The inspector should inspect from ground level, eaves or rooftop (if a rooftop access door exists):

A. the roof covering; B. for the presence of exposed membrane; C. slopes; D. for evidence of significant ponding; E. the gutters; F. the downspouts; G. the vents, flashings, skylights, chimney and other roof penetrations; H. the general structure of the roof from the readily accessible panels, doors or stairs; and I. for the need for repairs. II. The inspector is not required to:

A. walk on any pitched roof surface. B. predict service-life expectancy. C. inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions that prohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, lightning arresters, de-icing equipment or similar attachments. G. walk on any roof areas that appear, in the opinion of the inspector, to be unsafe. H. walk on any roof areas if it might, in the opinion of the inspector, cause damage. I. perform a water test. J. warrant or certify the roof. K. walk on any roofs that lack rooftop access doors.

Roof

Roof Drainage Systems

Gutter Material
Aluminum
Steel

Roof Views

Roof Inspection Method
Walked

Coverings

Roof covering Material
EPDM Rubber

1.1 · Roof Views

Roof Views - These are pictures or video of the roof at the time of the inspection.
General Information

1.2 · Coverings

Deteriorated Flat Roof Seams - The seams on the flat roof are deteriorated.
Repair or Replace

1.3 · Coverings

Ponding - The inspector observed ponding in one or more areas of roof. Ponding can lead to accelerated erosion and deterioration.
Further Evaluation

1.4 · Roof Drainage Systems

Damaged Gutter(s) and/or Downspout(s) - Gutters and/or downspouts were damaged. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement.
Repair or Replace

1.5 · Roof Drainage Systems

Loose Gutters/Downspouts - Gutter(s) and or downspout(s) are loose and need to be re-fastened to fascia or the building.
Repair or Replace

1.6 · Roof Drainage Systems

Gutters Leaking - Gutters were leaking in one or more areas. This can result in excessive moisture in the soil at the foundation, which can lead to foundation/structural movement.
General Maintenance

1.7 · Roof Drainage Systems

Debris In Gutter(s) - Debris has accumulated in the gutters. Recommend cleaning gutters and downspouts to facilitate water flow.
General Maintenance

2 · Exterior Section

Exterior Section

The inspector should inspect:

A. the siding, flashing and trim; B. all exterior doors, decks, stoops, steps, stairs, porches, railings, eaves, soffits and fasciae; C. and report as in need of repair any safety issues regarding intermediate balusters, spindles or rails for steps, stairways, balconies and railings; D. a representative number of windows; E. the vegetation, surface drainage, and retaining walls when these are likely to adversely affect the structure; F. the exterior for accessibility barriers; G. the storm water drainage system; H. the general topography; I. the parking areas; J. the sidewalks; K. exterior lighting; L. the landscaping; M. and determine that a 3-foot clear space exists around the circumference of fire hydrants; N. and describe the exterior wall covering. II. The inspector is not required to:

A. inspect or operate screens, storm windows, shutters, awnings, fences, outbuildings or exterior accent lighting. B. inspect items, including window and door flashings, that are not visible or readily accessible from the ground. C. inspect geological, geotechnical, hydrological or soil conditions. D. inspect recreational facilities. E. inspect seawalls, breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for proof of safety-type glass. H. determine the integrity of thermal window seals or damaged glass. I. inspect underground utilities.
J. inspect underground items. K. inspect wells or springs. L. inspect solar systems. M. inspect swimming pools or spas. N. inspect septic systems or cesspools. O. inspect playground equipment. P. inspect sprinkler systems. Q. inspect drainfields or dry wells. R. inspect manhole covers. S. operate or evaluate remote-control devices, or test door or gate operators. 6.5.3 Wood Decks and Balconies I. The inspector should inspect: A. with the unaided eye, for deck and balcony members that are noticeably out of level or out of plumb; B. for visible decay; C. for paint failure and buckling; D. for nail pullout (nail pop); E. for fastener rust, iron stain and corrosion; F. and verify that flashing was installed on the deck-side of the ledger board; G. for vertical members (posts) that have exposed end-grains; H. for obvious trip hazards; I. for non-graspable handrails; J. railings for height less than the 36-inch minimum*; K. guardrails and infill for openings that exceed the 4-inch maximum*; L. open-tread stairs for openings that exceed the 4⅜-inch maximum*; M. the triangular area between guardrails and stairways for openings that exceed the 6-inch maximum*; N. built-up and multi-ply beam spans for butt joints; O. for notches in the middle-third of solid-sawn wood spans; P. for large splits longer than the depths of their solid-sawn wood members; Q. for building egresses blocked, covered or hindered by deck construction; and R. for the possibility of wetting from gutters, downspouts or sprinklers.

*See https://www.nachi.org/stairways.htm for formal standards (compliance verification in entirety not required). II. The inspector is not required to: A. discover insect infestation or damage. B. inspect, determine or test the tightness or adequacy of fasteners. C. determine lumber grade. D. measure moisture content. E. inspect for or determine bending strength. F. inspect for or determine shear stress. G. determine lag screw or bolt shear values. H. calculate loads. I. determine proper spans or inspect for deflections. J. discover decay hidden by paint. K. verify that flashing has been coated to prevent corrosion. L. determine that post-to-footing attachments exist. M. dig below grade or remove soil around posts. N. crawl under any deck with less than 3 feet of headroom, or remove deck skirting to acquire access. O. determine proper footing depth or frostline. P. verify proper footing size. Q. perform pick tests. R. perform or provide any architectural or engineering service. S. use a level or plumb bob. T. use a moisture meter. U. predict service-life expectancy. V. verify compliance with permits, codes or formal standards. W. inspect for disabled persons' accessibility barriers. X. determine if a deck blocks, covers or hinders septic tank or plumbing access. Y. determine easement-encroachment compliance.

Exterior

Walkways, Patios And Driveways

Driveway Material
Asphalt
Sidewalk Material
Concrete

Siding, Flashing, And Trim

Siding Material
Brick
Masonry Block

Eaves, Soffits, And Fascia

Fascia Materials
Metal

Exterior Doors And Windows

Exterior Entry Door(s)
Metal

2.1 · Exterior Views

Exterior Views - These are pictures or video of the exterior at the time of the inspection.
General Information

2.2 · Siding, Flashing, And Trim

Exterior Finish Failing - The exterior finish in some areas is failing. A qualified person should prep (pressure wash, scrape, sand, prime caulk, etc.) and repaint or re-stain areas as needed and as per standard building practices.
General Maintenance

2.3 · Siding, Flashing, And Trim

Cracks In Brick/Mortar - Cracks and/or deterioration were found in one or more sections of brick and/or mortar. These are likely caused by movement of the foundation and/or walls.
Further Evaluation

2.4 · Siding, Flashing, And Trim

Deteriorated Caulking - Caulking is missing or deteriorated in some areas and should be replaced and/or applied where necessary.
General Maintenance

2.5 · Siding, Flashing, And Trim

Siding Damaged - Siding is damaged and/or deteriorated in one or more areas.
Repair or Replace

2.6 · Siding, Flashing, And Trim

Evidence Of Possible Rodents
Repair or Replace

2.7 · Siding, Flashing, And Trim

Loose Siding - Siding in one or more areas was loose, This can result in moisture intrusion or siding coming off.
Repair or Replace

2.8 · Siding, Flashing, And Trim

Gaps Around Penetrations - Gaps exist at one or more openings around the exterior, such as those where outside faucets, refrigerant lines, and/or gas supply pipes penetrate the exterior. Gaps should be sealed as necessary to prevent moisture intrusion and entry by vermin.
General Maintenance

2.9 · Decks, Balconies, Porches And Steps

Cracked/Deteriorated Concrete Support Base - one or more concrete supports are cracked or deteriorated.
Repair or Replace

2.10 · Decks, Balconies, Porches And Steps

Roof Support Columns Rotted - One or more porch roof support columns are rotted
Repair or Replace

2.11 · Walkways, Patios And Driveways

Driveway Cracked/Deteriorated - Cracking and/or deterioration was observed in one or more driveways(s).
Repair or Replace

2.12 · Walkways, Patios And Driveways

Walkway Cracking - Cracks were observed in one or more areas of walkways.
Repair or Replace

2.13 · Walkways, Patios And Driveways

Walkway Shrinkage Cracks - Shrinkage cracks were visible in the sidewalk at the time of the inspection. Recommend sealing the cracks to prevent further deterioration.
General Maintenance

2.14 · Walkways, Patios And Driveways

Reseal Asphalt - The asphalt driveway needs to be resealed. This is considered general maintenance for an asphalt driveway and will need to be performed every 1 to 3 years.
General Maintenance

2.15 · Walkways, Patios And Driveways

Trip Hazard(s) - Trip hazards were observed in one or more sections of the driveway(s), sidewalk(s), and/or patio(s).
Safety

2.16 · Exterior Doors And Windows

Rusted Door Frame
Repair or Replace

2.17 · Vegetation, Grading, Drainage And Retaining Walls

Vegetation To Close - Vegetation such as trees, shrubs and/or vines are in contact with or less than one foot from the structures exterior. Vegetation can serve as a conduit for wood destroying insects and may retain moisture against the exterior after it rains. Vegetation should be pruned and/or removed as necessary to maintain a one foot clearance between it and the structures exterior.
General Maintenance

2.18 · Vegetation, Grading, Drainage And Retaining Walls

Cracking In Retaining Wall - one or more crack(s) were found in retaining wall.
Repair or Replace

3 · Interior Section

Interior Section

The inspector should:

A. open and close a representative number of doors and windows; B. inspect the walls, ceilings, steps, stairways and railings; C. inspect garage doors and garage door-openers; D. inspect interior steps, stairs and railings; E. inspect all loading docks; F. ride all elevators and escalators; G. and report as in need of repair any windows that are obviously fogged or display other evidence of broken seals. II. The inspector is not required to:

A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect central-vacuum systems. C. inspect safety glazing. D. inspect security systems or components. E. evaluate the fastening of countertops, cabinets, sink tops or fixtures, or firewall compromises. F. move furniture, stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. G. move drop-ceiling tiles. H. inspect or move any appliances. I. inspect or operate equipment housed in the garage, except as otherwise noted. J. verify or certify safe operation of any auto-reverse or related safety function of a garage door. K. operate or evaluate any security bar-release and opening mechanisms, whether interior or exterior, including their compliance with local, state or federal standards. L. operate any system, appliance or component that requires the use of special keys, codes, combinations or devices. M. operate or evaluate self-cleaning oven cycles, tilt guards/latches, gauges or signal lights. N. inspect microwave ovens, or test leakage from microwave ovens. O. operate or examine any sauna, steam-jenny, kiln, toaster, ice maker, coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other ancillary devices. P. inspect elevators. Q. inspect remote controls. R. inspect appliances. S. inspect items not permanently installed. T. examine or operate any above-ground, movable, freestanding, or otherwise non-permanently installed pool/spa, recreational equipment, or self-contained equipment. U. come into contact with any pool or spa water in order to determine the system's structure or components. V. determine the adequacy of a spa's jet water force or bubble effect. W. determine the structural integrity or leakage of a pool or spa. X. determine combustibility or flammability. Y. inspect tenant-owned equipment or personal property.

Interior

Walls

Wall Material
Paint
Drywall
Wallpaper

Ceilings

Ceiling Material
Suspended Ceiling Panels

Floors

Floor Coverings
Vinyl
Laminate
Tile

3.1 · Interior Views

Interior Views - These are pictures or video of the interior at the time of the inspection.
General Information

3.2 · Ceilings

Damaged Ceiling(s) - Damage or deterioration to the ceiling(s) was visible at the time of the inspection. Hidden damage may be present.
Repair or Replace

3.3 · Ceilings

Dry Water Stains - Stains on the ceiling appear to be the result of water damage. The stains were dry at the time of the inspection.
Further Evaluation

3.4 · Walls

Damaged Walls(s) - Damage or deterioration to wall(s) was visible at the time of the inspection.
Repair or Replace

3.5 · Floors

Laminate Deteriorated - Laminate floors are deteriorating in one or more areas.
Repair or Replace

3.6 · Floors

Tile/Grout Deteriorated - Tile and or grout is deteriorated in one or more areas.
Repair or Replace

4 · Heating Section

Heating Section

The inspector should inspect:

A. multiple gas meter installations, such as a building with multiple tenant spaces, and verify that each meter is clearly and permanently identified with the respective space supplied; B. the heating systems using normal operating controls, and describe the energy source and heating method; C. and report as in need of repair heating systems that do not operate; D. and report if the heating systems are deemed inaccessible; E. and verify that a permanent means of access, with permanent ladders and/or catwalks, are present for equipment and appliances on roofs higher than 16 feet; F. and verify the presence of level service platforms for appliances on roofs with a slope of 25% or greater; G. and verify that luminaire and receptacle outlets are provided at or near the appliance; H. and verify that the system piping appears to be sloped to permit the system to be drained; I. for connectors, tubing and piping that might be installed in a way that exposes them to physical damage; J. wood framing with cutting, notching or boring that might cause a structural or safety issue; K. pipe penetrations in concrete and masonry building elements to verify that they are sleeved; L. exposed gas piping for identification by a yellow label marked "Gas" in black letters occurring at intervals of 5 feet or less; M. and determine if any appliances or equipment with ignition sources are located in public, private, repair or parking garages or fuel-dispensing facilities; N. and verify that fuel-fired appliances are not located in or obtain combustion air from sleeping rooms, bathrooms, storage closets or surgical rooms; O. for the presence of exhaust systems in occupied areas where there is a likelihood of excess heat, odors, fumes, spray, gas, noxious gases or smoke; P. and verify that outdoor air-intake openings are located at least 10 feet away from any hazardous or noxious contaminant sources, such as vents, chimneys, plumbing vents, streets, alleys, parking lots or loading docks; Q. outdoor exhaust outlets for the likelihood that they may cause a public nuisance or fire hazard due to smoke, grease, gases, vapors or odors; R. for the potential of flooding or evidence of past flooding that could cause mold in ductwork or plenums; and S. condensate drains. II. The inspector is not required to:

A. inspect or evaluate interiors of flues or chimneys, fire chambers, heat exchangers, humidifiers, dehumidifiers, electronic air filters, solar heating systems, fuel tanks, safety devices, pressure gauges, or control mechanisms. B. determine the uniformity, temperature, flow, balance, distribution, size, capacity, BTU, or supply adequacy of the heating system. C. light or ignite pilot flames. D. activate heating, heat pump systems, or other heating systems when ambient temperatures or other circumstances are not conducive to safe operation or may damage the equipment. E. over-ride electronic thermostats. F. evaluate fuel quality. G. verify thermostat calibration, heat anticipation or automatic setbacks, timers, programs or clocks. H. inspect tenant-owned or tenant-maintained heating equipment. I. determine ventilation rates. J. perform capture and containment tests. K. test for mold.

Heating

Heating Views

Heating Type
Forced Air
Fuel-Fired Boiler

Heating Equipment

Heating Brand
Bryant
York
Carrier

4.1 · Heating Views

Heating Views - These are pictures or video of the heating systems at the time of the inspection.
General Information

5 · Plumbing Section

Plumbing Section

The inspector should inspect:

A. and verify the presence of and identify the location of the main water shut-off valve to each building; B. and verify the presence of a back-flow prevention device if, in the inspector's opinion, a cross-connection could occur between the water-distribution system and non-potable water or private source; C. the water-heating equipment, including combustion air, venting, connections, energy-source supply systems, and seismic bracing, and verify the presence or absence of temperature-/pressure-relief valves and/or Watts 210 valves; D. and flush a representative number of toilets; E. and water-test a representative number of sinks, tubs and showers for functional drainage; F. and verify that hinged shower doors open outward from the shower, and have safety glass-conformance stickers or indicators; G. the interior water supply, including a representative number of fixtures and faucets; H. the drain, waste and vent systems, including a representative number of fixtures; I. and describe any visible fuel-storage systems; J. and test sump pumps with accessible floats; K. and describe the water supply, drain, waste and main fuel shut-off valves, as well as the location of the water main and main fuel shut-off valves; L. and determine whether the water supply is public or private; M. the water supply by viewing the functional flow in several fixtures operated simultaneously, and report any deficiencies as in need of repair; N. and report as in need of repair deficiencies in installation and identification of hot and cold faucets; O. and report as in need of repair mechanical drain stops that are missing or do not operate if installed in sinks, lavatories and tubs; P. and report as in need of repair commodes that have cracks in the ceramic material, are improperly mounted on the floor, leak, or have tank components that do not operate; and Q. piping support. II. The inspector is not required to:

A. determine the adequacy of the size of pipes, supplies, vents, traps or stacks. B. ignite pilot flames. C. determine the size, temperature, age, life expectancy or adequacy of the water heater. D. inspect interiors of flues or chimneys, cleanouts, water-softening or filtering systems, dishwashers, interceptors, separators, sump pumps, well pumps or tanks, safety or shut-off valves, whirlpools, swimming pools, floor drains, lawn sprinkler systems or fire sprinkler systems. E. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. F. verify or test anti-scald devices. G. determine the water quality, potability or reliability of the water supply or source. H. open sealed plumbing access panels. I. inspect clothes washing machines or their connections. J. operate any main, branch or fixture valve. K. test shower pans, tub and shower surrounds, or enclosures for leakage. L. evaluate compliance with local or state conservation or energy standards, or the proper design or sizing of any water, waste or venting components, fixtures or piping. M. determine the effectiveness of anti-siphon, back-flow prevention or drain-stop devices. N. determine whether there are sufficient cleanouts for effective cleaning of drains. O. evaluate gas, liquid propane or oil-storage tanks. P. inspect any private sewage waste-disposal system or component within such a system. Q. inspect water-treatment systems or water filters. R. inspect water-storage tanks, pressure pumps, ejector pumps, or bladder tanks. S. evaluate wait time for hot water at fixtures, or perform testing of any kind on water-heater elements. T. evaluate or determine the adequacy of combustion air. U. test, operate, open or close safety controls, manual stop valves, or temperature- or pressure-relief valves. V. examine ancillary systems or components, such as, but not limited to, those relating to solar water heating or hot-water circulation. W. determine the presence or condition of polybutylene plumbing.

Plumbing

Main Water Shut Off Location

Main Water Shut Off Location
At Meter

Main Gas Shut-Off Location

Main Gas Shut-off Location
At Meter

Main Water Shut-off Device

Water Source
Public

Hot Water Systems, Controls, Flues & Vents

Water Heater Brand
State

Water Heater Power Source

Water Heater Power Source
Gas

5.1 · Plumbing Views

Plumbing Views - These are pictures or video of the plumbing systems at the time of the inspection.
General Information

5.2 · Plumbing Limitations

Water Shut Off - The main water was turned off at the time of the inspection. The water system was not evaluated. Recommend having the water turned on and the system evaluated.
Limitations

5.3 · Main Gas Shut-Off Location

Main Gas Shut Off
General Information

5.4 · Fuel Storage & Distribution Systems

Gas Pipe Rust - Significant amounts of rust or corrosion were found on one or more gas supply pipes. Based on this deterioration, the wrong materials may have been used. For example, black iron pipe may have been used where galvanized iron pipe should have been used instead. Leaks may occur as a result. This is a safety hazard.
Safety

5.5 · Main Water Shut Off Location

Main Water Shut Off Location
General Information

5.6 · Water Heater Views

Water Heater Views - These are pictures or video of the water heater at the time of the inspection.
Further Evaluation

5.7 · Hot Water Systems, Controls, Flues & Vents

Corrosion On Fittings - Corrosion was found on fittings and/or water supply lines for the water heater. Leaks may exist.
Repair or Replace

5.8 · Drain, Waste, & Vent Systems

Past Leaks - Stains were found in one or more sections of drain and/or waste pipes. Recommend monitoring these areas in the future, and if leaks are found, have a qualified plumber evaluate and repair as necessary.
Further Evaluation

5.9 · Drain, Waste, & Vent Systems

Active Drain Leak - One or more active leaks were found in drain and/or waste pipes or fittings.
Repair or Replace

6 · Electrical Section

Electrical Section

The inspector should inspect:

A. the service drop/lateral; B. the meter socket enclosures; C. the service-entrance conductors, and report on any noted deterioration of the conductor insulation or cable sheath; D. the means for disconnecting the service main; E. the service-entrance equipment, and report on any noted physical damage, overheating or corrosion; F. and determine the rating of the service disconnect amperage, if labeled; G. panelboards and over-current devices, and report on any noted physical damage, overheating, corrosion, or lack of accessibility or working space (minimum 30 inches wide, 36 inches deep, and 78 inches high in front of panel) that would hamper safe operation, maintenance or inspection; H. and report on any unused circuit-breaker panel openings that are not filled; I. and report on absent or poor labeling; J. the service grounding and bonding; K. a representative number of switches, lighting fixtures and receptacles, including receptacles observed and deemed to be AFCI-protected using the AFCI test button, where possible. Although a visual inspection, the removal of faceplates or other covers or luminaires (fixtures) to identify suspected hazards is permitted; L. and report on any noted missing or damaged faceplates or box covers; M. and report on any noted open junction boxes or open wiring splices; N. and report on any noted switches and receptacles that are painted; O. and test all ground-fault circuit interrupter (GFCI) receptacles and GFCI circuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; P. and report the presence of solid-conductor aluminum branch-circuit wiring, if readily visible; Q. and report on any tested GFCI receptacles in which power was not present, polarity was incorrect, the cover was not in place, the GFCI devices were not installed properly or did not operate properly, any evidence of arcing or excessive heat, or where the receptacle was not grounded or was not secured to the wall; R. and report the absence of smoke detectors; S. and report on the presence of flexible cords being improperly used as substitutes for the fixed wiring of a structure or running through walls, ceilings, floors, doorways, windows, or under carpets. II. The inspector is not required to:

A. insert any tool, probe or device into the main panelboard, sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C. remove panelboard cabinet covers or dead fronts if they are not readily accessible. D. operate over-current protection devices. E. operate non-accessible smoke detectors. F. measure or determine the amperage or voltage of the main service equipment, if not visibly labeled. G. inspect the fire or alarm system and components. H. inspect the ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. operate or reset overload devices. K. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring, or any time-controlled devices. L. verify the service ground. M. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills, photovoltaic solar collectors, or the battery- or electrical-storage facility. N. inspect spark or lightning arrestors. O. inspect or test de-icing equipment. P. conduct voltage-drop calculations. Q. determine the accuracy of labeling. R. inspect tenant-owned equipment. S. inspect the condition of or determine the ampacity of extension cords.

Electrical

Electrical Service Entrance Views

Electrical Service Type
Below Ground

Main & Subpanels, Service & Grounding, Main Overcurrent Device

Panel(s) Manufacturer
Siemens

Electrical Service Entrance

Electrical Service Conductors
240 Volts

6.1 · Electrical Service Entrance Views

Electrical Service Entrance Views - These are pictures or video of the Electrical Service Entrance at the time of the inspection.
General Information

6.2 · Electrical Service Entrance

Rusted Electrical Service - Rusted Service Panel.
Repair or Replace

6.3 · Main & Subpanels Views

Main & Subpanel Views - These are pictures or video of the Main & Subpanel(s) at the time of the inspection.
General Information

6.4 · Main & Subpanels, Service & Grounding, Main Overcurrent Device

Inadequate Working Space - Inadequate working space exists for the main service panel. Standard building practices require the following clearances: -An area 30 inches wide by 3 feet deep exists in front of the panel -The panel is at least 5 1/2 feet above the floor -There is at least 6 feet 6 inches of headroom in front of the panel -The wall below the panel is clear to the floor
Repair or Replace

6.5 · Lighting Fixtures, Switches & Receptacles

Bad Ground - One or more receptacles bad grounding.
Safety

6.6 · Lighting Fixtures, Switches & Receptacles

Painted Over - One or more switches and/or receptacles have been painted over.
Repair or Replace

6.7 · Lighting Fixtures, Switches & Receptacles

Cover Plates Missing - One or more receptacles or junction boxes are missing a cover plate. This causes short and shock risk.
Safety

6.8 · GFCI & AFCI

GFCI Missing Outdoor Protection Cover
Safety

6.9 · GFCI & AFCI

GFCI Didn't Trip - One or more ground fault circuit interrupter (GFCI) electric receptacles did not trip when tested. This is a safety hazard due to the risk of shock.
Safety

7 · Attic, Insulation, and Ventilation Section

Attic, Insulation, and Ventilation Section

The inspector should inspect:

A. the insulation in unfinished spaces; B. the ventilation of attic spaces; C. mechanical ventilation systems;
D. and report on the general absence or lack of insulation. II. The inspector is not required to:

A. enter the attic or any unfinished spaces that are not readily accessible, or where entry could cause damage or pose a safety hazard to the inspector, in his or her opinion. B. move, touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surface finish or weather seal on or around access panels or covers. E. identify the composition or exact R-value of insulation material. F. activate thermostatically operated fans. G. determine the types of materials used in insulation or wrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.

Attic, Insulation, and Ventilation

7.1 · Roof Structure & Attic

Rotted Wood Roof Support Beam - One or more area(s) of wood roof support beam(s) were rotted.
Repair or Replace

7.2 · Roof Structure & Attic

Joists Pulling Away From Ledger Board - One or more area(s) of joist(s) are pulling away from ledger board.
Further Evaluation

8 · Life Safety Section

Life Safety Section

The inspector should: A. inspect fire access roads and report on any obstructions or overhead wires lower than 13 feet and 6 inches; B. inspect the address or street number to determine whether it is visible from the street, with numbers in contrast to their background; C. inspect to determine whether a 3-foot clear space exists around the circumference of fire hydrants; D. verify that hinged shower doors open outward from the shower and have safety glass-conformance stickers or indicators; E. inspect to determine whether the storage of flammable and combustible materials is orderly, separated from heaters by distance or shielding so that ignition cannot occur, and not stored in exits, boiler rooms, mechanical rooms or electrical equipment rooms; F. inspect to determine whether a "No Smoking" sign is posted in areas where flammable or combustible material is stored, dispensed or used; G. inspect for the presence of fire alarm systems; H. inspect for alarm panel accessibility; I. inspect for the presence of portable extinguishers, and determine whether they are located in conspicuous and readily available locations immediately available for use, and not obstructed or obscured from view; J. inspect to determine whether a portable fire extinguisher is stored within a 30-foot travel distance of commercial-type cooking equipment that uses cooking oil or animal fat; K. inspect to determine whether manual-actuation devices for commercial cooking appliances exist near the means of egress from the cooking area, 42 to 48 inches above the floor and 10 and 20 feet away, and clearly identifying the hazards protected; L. inspect to determine whether the maximum travel distance to a fire extinguisher is 75 feet; M. inspect for the presence of sprinkler systems, and determine if they were ever painted other than at the factory; N. inspect for the presence of emergency lighting systems; O. inspect for exit signs at all exits, and inspect for independent power sources, such as batteries; P. inspect for the presence of directional signs where an exit location is not obvious; Q. inspect for the presence of signs over lockable exit doors stating: "This Door Must Remain Unlocked During Business Hours"; R. inspect for penetrations in any walls or ceilings that separate the exit corridors or stairwells from the rest of the building; S. inspect for fire-separation doors that appear to have been blocked or wedged open, or that do not automatically close and latch; T. inspect exit stairwell handrails; U. inspect for exit trip hazards; V. inspect for the presence of at least two exits to the outside, or one exit that has a maximum travel distance of 75 feet; W. inspect exit doorways to determine that they are less than 32 inches in clear width; X. inspect to determine whether the exit doors were locked from the inside, chained, bolted, barred, latched or otherwise rendered unusable at the time of the inspection; Y. inspect to determine whether the exit doors swing open in the direction of egress travel; and Z. inspect the storage to determine if it is potentially obstructing access to fire hydrants, fire extinguishers, alarm panels or electric panelboards, or if it is obstructing aisles, corridors, stairways or exit doors, or if it is within 18 inches of sprinkler heads, or if it is within 3 feet of heat-generating appliances or electrical panelboards. II. The inspector is not required to: A. test alarm systems, or determine if alarms systems have been tested. B. inspect or test heat detectors, fire-suppression systems, or sprinkler systems. C. determine the combustibility or flammability of materials in storage. D. determine the adequate number of fire extinguishers needed, or their ratings. E. test or inspect fire extinguishers, their pressure, or for the presence of extinguisher inspection tags or tamper seals. F. inspect or test fire pumps or fire department connections. G. inspect or test cooking equipment suppression systems. H. determine the operational time of emergency lighting or exit signs. I. inspect for proper occupant load signs. J. determine fire ratings of walls, ceilings, doors, etc. K. inspect, test or determine the adequacy of fire escapes or ladders. L. inspect fire department lock boxes or keys. M. determine the flame resistance of curtains or draperies. N. inspect parking or outdoor lighting. O. inspect for unauthorized entry or crime issues. P. inspect or test security systems. Q. inspect for pet or livestock safety issues. R. inspect for unsafe candle use or decoration hazards. S. inspect or test emergency generators. T. test kitchen equipment, appliances or hoods. U. verify that elevator keys exist, or that they work properly.

Life Safety

8.1 · Portable Fire Extinguishers (in readily available locations)

Fire extinguishers out of date Fire extinguishers need to be checked annually and or replaced.
N/A